Safety First. Records matter, let us drill down on what needs recording as part of your fire safety.
What is a fire log book? Why does your business need one? What should you record?
In business we tend to have to record everything, and this is for a very valid reason at any point anyone coming into the company can see that there are records for all situations.
For instance, If an employee noticed that the fire extinguisher in the warehouse had been tampered with but failed to record it. A month or so later a fire started and another employee reached for that extinguisher and it was damaged. That fire has now doubled in size and by the time someone has found an intact extinguisher the building is now highly ablaze and serious intervention is needed. What could have been an alternative scenario?
The employee noticed on the weekly inspection that an extinguisher was damaged, they recorded in the fire log book that the extinguisher was damaged and called their fire safety company. Disaster averted.
It is good to note that everything to do with your fire safety needs to be recorded, in this article we will try and address all points on a fire safety log.
Why keeping an accurate fire log is so important for the safety of your employees and your business
With numerous fire safety regulations in force across the United Kingdom and frequent changes to The Regulatory Reform (Fire Safety) Order 2005, commercial and industrial property managers must stay ahead and understand their fire safety responsibilities.
Fire safety is non-negotiable. Incidents like the 2017 Grenfell Tower fire have highlighted the dangers of ignoring regulations, leading to devastating consequences. Effective fire safety involves more than just installing the right equipment. Maintaining a thorough record of fire safety equipment testing and fire events or tests are crucial to ensure a detailed and systematic approach to fire prevention.
Why Weekly Testing Matters
Conducting weekly fire alarm test, visual check of fire extinguishers and emergency lighting in your business premises is essential, but without a formal record, it becomes challenging to prove compliance with legal obligations. As well as equipment checks a fire evacuation should be carried out on a regular basis
In the event of a fire, if questions arise about the effectiveness of your evacuation procedures, your business may face severe financial penalties and reputational damage if it cannot demonstrate consistent weekly tests.
A fire alarm log allows you to identify and address any system issues. By recording your findings and documenting all maintenance and servicing or repair actions, you provide evidence of a proactive approach to fire safety in the workplace.

Ensuring Compliance with Fire Regulations: What Your Business Needs to Know
To ensure compliance with fire regulations, every business must maintain a fire safety logbook. This logbook helps track fire risk procedures, safety training, and monitoring activities, ensuring they are completed and up-to-date. Compliance with the Regulatory Reform (Fire Safety) Order 2005 (RRFSO 05) mandates keeping this logbook. Below are steps to help your business stay compliant with fire safety regulations.
Safety Equipment Testing and Maintenance
A fire logbook should contain detailed information about the companies or individuals responsible for testing and maintaining your safety equipment. This log should include a comprehensive record of all safety checks, along with their completion dates. Essential items to record include Fire Alarm testing, Fire Extinguisher testing, Emergency Lighting testing, Fire Suppression Systems testing, and full maintenance activities. Weekly fire alarm tests must be conducted by the designated responsible person, with any issues or concerns documented in the logbook.
The Importance of a Fire Alarm Test Log
According to BS 5839-1:2017 (Fire detection and fire alarm systems for buildings), fire alarm testing requirements in commercial premises must be tested weekly. Regular testing ensures that the systems function properly, significantly reducing the risk of equipment failure if a fire should arise.
By law, maintaining a fire alarm log book is mandatory for all commercial premises with a fire alarm system and control panel. This requirement, outlined in The Regulatory Reform (Fire Safety) Order 2005, helps premises managers and property owners comply with BS5839 standards.
FIRE ALARM TESTING REQUIREMENTS
In order to satisfy the recommendations of BS 5839-1, the following need to be recorded within your fire log book:
- The names of the premises management team or owners
- Dates of equipment installation
- Brief details of the maintenance arrangements
- Dates and times of all equipment tests
- Dates and times of all fires to which the system responds
- Dates and times of all false alarms
- Causes, circumstances surrounding, and category, of all false alarms (if known)
- The identity of any manual call point or automatic fire detector that triggers any of the above fire alarm signals (if known)
- Dates, times and types of all faults and defects
- Dates and types of all maintenance (e.g. service visit or non-routine attention)
- Dates and times of all fire drills
- Dates and times of all staff training


FIRE ALARM ACTIVATION AND FALSE ALARMS
All incidents of a fire alarm activations should be recorded regardless of whether an actual fire has occurred. In order to ensure alerts are dealt with by staff in a timely fashion and taken seriously we also need to ensure that there are minimal false alarms in any given period. Regular unnecessary fire alarms can cause complacency in the workplace which increases risk.
If there is no attempt by the relevant member of the premises management to limit false alarms, the Fire Alarm System should no longer be considered as compliant with BS 5839-1.” Categories of False Alarm (clause 31 of BS 5839-1) To minimise risks we need to ensure 4 risk areas are avoided;
- The creation of fire-like incidents such as heat from working activity, smoke from equipment or dust. These can be avoided by ensuring safety audits and risk assessments are completed and implemented correctly.
- System Fault Errors These errors should be avoided through proper fire monitoring system Design, Installation and Maintenance.
- Malicious False Alarms These risks can be limited through staff training and limiting access to workplaces to prevent outside tampering.
- False Alarms where someone makes an honest mistake These risks can be avoided by ensuring that adequate fire safety training is completed.
Acceptable Incident Levels by Industry Standards
Industry standards states acceptable incident levels, which vary by sector and business size. The framework below outlines acceptable incident rates based on business type and equipment:
- Office areas (non-smoking, no cooking, clean, well-managed): Aim for no more than 1 false alarm per 100 detectors annually.
- Industrial sites with shift work: Aim for no more than 1 false alarm per 75 detectors annually.
- Modern technology typically results in a rate of no more than 1 false alarm per 50 detectors annually.
For sites with more than 40 detectors, conduct an in-depth investigation and take action to reduce false alarms if:
- The average annual rate exceeds 1 per 20 detectors.
- The same call point, detector, or location triggers 3 or more false alarms within a rolling 12-month period.
- For sites with fewer than 40 detectors, investigate if 3 or more false alarms occur within a rolling 12-month period.
Staff Training
It is advisable to train all staff at the start of their employment and provide annual refresher training for all team members. Conduct regular fire drills to ensure the premises can be evacuated quickly and efficiently, these drills should be carried out at least twice a year. Record the fire drill times and any issues in your fire log book. Keep your log book up to date, and ensure your fire maintenance contractors provide all necessary paperwork and documentation.
Appointing a Responsible Person to Undertake a Fire Alarm Test
Designate the fire protection responsibility to a named Responsible and competent Person, such as a professional fire alarm maintenance company. This person should conduct weekly fire alarm tests and record them in the fire log book. If you appoint a staff member, provide them with advanced training to ensure they complete the task correctly.